Ask a property manager which piece of equipment generates the most complaints, and the answer is almost never the one people expect.

It is not the boiler. It is the make-up air unit sitting on the roof, quietly deciding how every corridor and every suite in the building feels.

What a make-up air unit actually does

In most mid-rise and high-rise residential buildings, suites do not draw outdoor air directly. The make-up air unit does it for them.

The unit pulls in outdoor air, tempers it by heating or cooling, and delivers it to the corridors. That slightly pressurizes the corridor relative to the suites. Air then migrates from the corridor into each suite through the undercut beneath the door, and leaves through bathroom and kitchen exhaust.

The corridor is not just a hallway. It is the building’s air distribution path.

Once that is clear, a lot of seemingly unrelated complaints start making sense.

Why the complaint never matches the cause

Residents do not report make-up air problems. They report symptoms, and the symptoms sound like six different issues.

A suite that will not stay warm in winter, even with the in-suite heat running. A suite that is stuffy and will not clear. Cooking smells from a neighbour’s unit appearing in the hallway or in someone else’s suite. Corridor doors that slam, or that take real effort to open. Whistling around suite doors. Stairwell doors that are difficult to close properly.

All six trace back to corridor pressure. When the make-up air unit is delivering less than it should, or nothing at all, the corridor loses its positive pressure. Air stops moving in the intended direction and starts moving wherever the building’s own pressure differences take it. That is how one unit’s cooking ends up in another unit’s living room.

It is also why chasing these complaints one suite at a time rarely works. Six service calls to six suites can all come back to one unit on the roof. We have written more about buildings that stay uncomfortable even with cooling running.

The common failures

Five, roughly in order of how often we see them.

Heating section failure. Burners, ignition components and gas valves fail, and the unit continues moving air. It just moves outdoor air at outdoor temperature straight into the corridors. In January this produces a flood of complaints within hours.

Sensor drift or failure. Discharge air and outdoor air sensors lose accuracy over time. The unit is not broken, but it is responding to information that is wrong, so it heats to the wrong setpoint or fails to respond to a temperature swing.

Stuck dampers. Outdoor air dampers, return dampers and actuators seize, particularly after a season of not moving. A damper stuck closed starves the building. A damper stuck open overwhelms the heating section in cold weather.

Fan, belt and motor issues. Belts loosen and slip, bearings wear, motors fail. Airflow drops gradually, which makes this one hard to notice. The building slowly gets worse and nobody can point to the day it changed.

Controls left in a seasonal mode. Common, avoidable, and surprisingly persistent. A unit switched to summer operation in May and never switched back in October. Nothing is broken. Nobody changed the setting.

Stack effect and why winter is worse

Tall buildings behave like chimneys. Warm interior air is lighter than cold outdoor air, so it rises through stairwells, elevator shafts and service risers and tries to leave at the top, drawing cold air in at the bottom.

The bigger the temperature difference, the stronger the effect. Which is why complaints spike in January and disappear in May, and why the pattern is usually vertical. Lower floors feel cold and draughty while upper floors feel overheated and stuffy.

A properly functioning make-up air unit counteracts this by maintaining corridor pressure. A failing one lets stack effect run the building instead, which is why the same equipment fault produces different complaints on different floors of the same tower.

Who is responsible for the make-up air unit

In most condominium corporations the make-up air unit is a common element, because it serves the corridors and the building as a whole rather than any individual suite. That normally makes it the corporation’s responsibility to maintain and replace.

Normally is doing work in that sentence. Responsibility is determined by the corporation’s declaration and description, and those documents vary. Boards and property managers should confirm against their own governing documents rather than assume the common arrangement applies.

This article is general information and not legal advice. Our guide to who is responsible for HVAC in a condo covers the division in more detail, and our condo HVAC FAQ answers the questions boards ask most often.

What maintenance should cover

A make-up air unit needs attention at least twice a year, aligned with the seasonal changeover, and the changeover itself should be a scheduled visit rather than something someone remembers.

A proper visit covers the heating section and burner operation, sensor calibration against a reference, damper and actuator movement through the full range, belt tension and fan condition, filter replacement, and a verification that the unit is actually in the correct seasonal mode with the correct setpoints.

Corridor pressure is worth measuring rather than assuming. It is the one number that tells you whether the system is doing its job, and very few buildings track it.

Where a building has automation, all of this can be monitored continuously, and a failed heating section becomes an alert rather than a Monday morning of phone calls.

New buildings are not exempt

There is a common assumption that a new building will not have these problems for years. In practice, the first year is when commissioning issues surface.

Setpoints left at construction values. Sensors never calibrated. Balancing completed before the building was fully occupied. Controls programmed by someone who has since left the project. None of these are defects exactly, which is why they often fall outside a warranty claim, and all of them produce exactly the symptoms above.

This is worth attention in Grimsby in particular, where a significant amount of new condominium and purpose-built rental stock has come online recently. It applies equally to newer buildings in Hamilton and St. Catharines.

Starting a maintenance program in year one protects the warranty, establishes a performance baseline, and catches commissioning issues while somebody else is still responsible for correcting them.

Alpine works with condominium corporations and property managers across Niagara, Hamilton and the Golden Horseshoe. Contact us to arrange a make-up air assessment for your building.

REACH OUT FOR A FREE QUOTE

Reach out to us for a free quote or a low-cost, no-obligation consultation. Our team is happy to learn more about your needs and provide HVAC help to everyone who needs it, when you need it.

Whether you need boiler repairs, chiller installation, or routine maintenance, we provide prompt, professional service backed by years of experience. Our team of certified HVAC technicians are here to ensure your business stays comfortable year-round.

Reach us directly by calling (289) 438-1175
Alpine HVAC Logo
Alpine HVAC Service Inc BBB Business Review
4241 Victoria Avenue
Vineland Station, ON | L0R 2E0
Alpine HVAC. All Rights Reserved. 2025.
Site Designed by Giant Shoe Creative Agency.